When a steel beam or concrete lintel bears onto brickwork or blockwork, the load is concentrated at the two end points. If that concentration of stress is too high, the masonry below simply crushes — sometimes immediately, sometimes gradually over weeks as the mortar beds compact.
This is why padstone design for masonry is a critical part of any beam installation — not an afterthought.
Correct padstone design for masonry means selecting a solid, high-strength block — usually precast concrete, dense aggregate concrete block, or engineering brick — placed at the bearing point of a beam or lintel. Its job is purely structural: distribute load, reduce stress.
Standard hollow or aerated blocks (the lightweight ones used in most inner leaves) are not strong enough to carry a concentrated beam reaction. They will crack. A padstone replaces that weak block with something purpose-made for the job.
Padstones are not optional on loadbearing beam installations. They are a specified structural element. If an engineer's drawings show a padstone and the builder omits it or substitutes a standard block, the installation is non-compliant and Building Control will not sign it off.
The calculation is straightforward in principle. We know the beam reaction at the support (in kilonewtons), and we know the allowable bearing stress of the masonry below (in N/mm²). From these two numbers we get the minimum required bearing area:
The allowable bearing stress depends on the masonry unit strength and mortar designation. For standard coursed brickwork with a general-purpose mortar, this is typically in the range of 0.4 to 1.1 N/mm² depending on the brick class and mortar strength. Dense concrete blocks are generally stronger.
The padstone itself also needs to be strong enough to spread the load without cracking. Good padstone design for masonry means specifying precast concrete at 40N/mm² minimum. Standard aerated or medium-density blocks are typically 7–10N/mm² — completely inadequate for this application.
The table below gives typical sizes used in padstone design for masonry in common residential scenarios. These are indicative only — the correct size for your project depends on the actual beam reaction and masonry strength, and should be confirmed by a structural engineer.
| Scenario | Typical Padstone Size | Notes |
|---|---|---|
| Short lintel (1.2–2.0m), light load | 215mm × 100mm × 65mm | Engineering brick or dense block. Often omitted in error on light openings. |
| Standard wall removal (2.0–3.5m span) | 440mm × 215mm × 100mm | Precast concrete at 40N/mm². Most common size in residential practice. |
| Heavy load — floor joists + roof above (3.0–4.5m) | 440mm × 215mm × 150mm | Deeper section for higher reactions. Check masonry courses align. |
| Bi-fold door opening, cavity wall (2.4–3.6m) | 440mm × 100mm × 215mm | Narrower to fit inner leaf only. Outer leaf checked separately. |
| Wide opening with concentrated point load (4.0m+) | 600mm × 215mm × 150mm+ | Or consider spreader plate welded to beam flange. Engineer to confirm. |
Using a cut or snapped block as a padstone. A cut half-block has no bond to adjacent masonry and concentrates load onto a fragment. It will crack, and the beam will settle. This is the single most common bearing defect we see on site inspections.
Under-sizing to suit available stock. If your builders' merchant only has 215mm × 215mm pads and the engineer specified 440mm × 215mm, the builder needs to contact the engineer — not use what is available. The padstone design for masonry is based on calculated bearing area, not site convenience.
Omitting the padstone on the inner leaf of a cavity wall. In a cavity wall, the steel beam typically bears onto the inner leaf. The outer leaf carries its own load through the cavity wall ties. But the inner leaf bearing absolutely must have a padstone. We occasionally see lintels bedded directly onto thin-joint aerated blocks — this will fail.
Not aligning with a full mortar bed. The padstone must sit on a full, level mortar bed. If the course heights do not work out neatly, adjust the coursing — do not dry-pack or wedge a padstone into place. An uneven bearing concentrates load onto one corner and is a common cause of early cracking.
Padstone design for masonry is not just for steel beams. Heavily loaded lintels — particularly those spanning wide openings or carrying floor loads — also require padstones at their bearing points for the same reason.
The general rule: if the lintel is carrying more than the weight of a small triangular wedge of masonry (i.e. arching action cannot be relied upon), check whether the end bearing stress exceeds the masonry capacity. If it does, a padstone is required.
← See the full Lintel Design & Detailing guide Wall Removal Calculations service →
Can I use an engineering brick instead of a precast padstone?
Yes, in many cases. A Class B engineering brick (typically 50N/mm²) provides excellent bearing capacity and integrates neatly into brickwork courses. The key is using a full, solid unit with no perforations at the bearing point, and confirming the bearing area is adequate for the load.
Does every lintel need a padstone?
No. For short, lightly loaded spans with full arching action above and competent masonry below, standard brickwork at the bearing point is often adequate. The engineer will check this as part of the lintel design. For spans over 2m on loadbearing walls, a padstone is almost always specified.
Where do I buy precast concrete padstones?
Most builders' merchants stock standard sizes (215mm × 215mm and 440mm × 215mm) in 40N/mm² precast concrete. For non-standard sizes, any precast concrete manufacturer can cast to order with a few days' lead time.
Need padstone sizes calculated for your project? Send us the details and we'll include them in your calculation package.
